🔐 SIL Safety Integrity Level
Required SIL for a SIF from the Risk Reduction Factor (RRF) or PFDavg (IEC 61511)
🔧 All Tools
SIL Determination
SIL Levels (IEC 61511)
SILPFDavg (probability of failure on demand)RRFDescription
Below SIL 1> 1×10⁻¹< 10Generally no SIL management required
SIL 11×10⁻¹ ~ 1×10⁻²10 ~ 100Risk reduction 10~100x
SIL 21×10⁻² ~ 1×10⁻³100 ~ 1000Risk reduction 100~1000x
SIL 31×10⁻³ ~ 1×10⁻⁴1000 ~ 10000High-risk scenario; redundant architecture + high diagnostic coverage required
> SIL 3≤ 1×10⁻⁴≥ 10000Multiple independent SIFs or special design recommended
· Architecture reference: basic 1oo1 typically reaches SIL 1~2; 1oo1 with diagnostics, or 1oo2 / 2oo3, can reach SIL 2~3.

About SIL Safety Integrity Level

SIL calculator per IEC 61508/61511: compute PFDavg and risk reduction factor, then map to SIL 1-4 requirements for SIF rating.